SLU-A22 (TypeF) Safety Isolated Barriers

SLU-A22 (TypeF)  Safety Isolated Barriers

SLU-A22 (TypeF)

Safety Isolated Barriers

Input

As per details

Output

As per details

Dimension

45.5×113.5×100mm

Email: sales@transducersgroup.com

More details


SLU-A22 (TypeF)Safety Isolated Barriers

 

1.Technical Parameters:


1)Main functions and features

● Compact and insert-mounting
● Input circuit Intrinsic Safety, [Exib]ⅡC if suitably certified.
● The supply of power to two independent 2-wire transmitters
● Power supply for field transmitter, and prevent hazardous energy from the instrinsically safety terminal into the hazardous area, transfer the DC signal to isolated standard process signal.
● With power indicator, Zero & Span adjustment for output signal
● Two independent input channels & output channels, each channel ”Input, output and power supply “are isolated from each other

 

2)Input (hazardous-area signal)
●  Current input:  current: 4~20mA, 
    Input resistance: 50Ω (built-in)
●  Voltage input:  voltage: 1~5V, 
    Input resistance: ≥50 KΩ 
●  RTD input (Pt100):  input signal: -200℃~+800℃


3)  output (safe-area signal) 
●  Current output:  Current: 4~20mA, 
    Load resistance: ≤500Ω
●  Voltage output:  voltage: 1~5V, 
    Load resistance: ≥10 KΩ


 4) Intrinsic safety:   

● Explosion-proof: [Exib]ⅡC
● Max. Voltage Um: 250V
● Max. Output voltage Uo: 30V
● Max. Output current Io: 30mA
● Max. External inductance Lo: 10mH
● Max. External Capacity Co: 0.066μF


5) Environmental parameters: 
● Power supply: DC24V±10%, current consumption 5W when aftereffect Wpp < 10%
● Temperature: -20 ~ +60 ℃
● Humidity: 10%~85%RH (none congeal)


2. Performance index (to full span)
● Standard accuracy: ±0.2% FS
● Temperature drift: ±0.02%/℃
● Response time: ≤0.5s (0→90%)
● Power voltage affect: ±0.2%/permitted voltage range
● Insulated resistance: 
   Input, output and power supply are isolated from each other ≥50 MΩ/DC 500V
● Isolation intensity: input-output-power supply-ground: 
   DC 1500V/1 minute (DC power)
   AC 1500V/1 minute (AC power)
● load resistance affect: ±0.2%/500Ω (when current output)
                                   ±0.2% (when voltage output)
● Settling time: ≤3s


3. Construction and dimension
● Structure: compact, insert-mounting
● Connection: 3mm connection terminal
● Terminal screw material: nickel plating around surface of iron 
   (screw arrowed wrest<0.8N•m)
● Shell material: burn-bear colophony
● Isolation: channel isolation (input,output and power supply are isolated from each othe)
● Zero adjustments-range: -5 ~ +5% 
● Span adjustments-range: 95~105%
● Power indicate light: green LED, light on when power supply
● Mounting: DIN rail 
● Outline dimension (W×H×D): 45.5×113.5×100mm
● Net weight: app. 500 g