SLU-A11 (TypeS) Safety Isolated Barriers
1. Technical Parameters:
1) Main functions and features
● Compact and insert-mounting
● Input circuit Intrinsic Safety, [Exib]ⅡC if suitably certified.
● The supply of power to 2-wire transmitters
● Power supply for field transmitter, and prevent hazardous energy from the instrinsically safety terminal into the hazardous area, transfer the DC signal to isolated standard process signal.
● With power indicator, Zero & Span adjustment for output signal
● Input, output and power supply are isolated from each other
● Linear to temperature (T.C, RTD)
2)Input (hazardous-area signal)
● Current input: current: DC 4~20mA,
Voltage supply: 18.5~28.5 V,
Input resistance: 50Ω (built-in)
● Voltage input: voltage: 1~5V,
Input resistance: ≥50 KΩ
● Input: T.C
Signal source: types K, E, S, B, R, T, N, W, J or millivlt
| T.C | Range ability (℃) | Minimum range (℃) |
| K | 0-1300 | 120 |
| E | 0-1000 | 80 |
| S | 0-1600 | 580 |
| B | 400-1800 | 1000 |
| R | 0-1600 | 850 |
| T | .-200-400 | 120 |
| N | 0-1200 | 180 |
| W | 0-2300 | 340 |
| J | 0-1200 | 100 |
| Input resistance: ≥20 KΩ | ||
| Minimum signal: ≥5mV | ||
● Input: RTD
| RTD | Range ability (℃) | Minimum range (℃) |
| Cu50 | -50-150 | 50 |
| Cu100 | -50-150 | 50 |
| Pt10 | -200-600 | 200 |
| Pt100 | -200-600 | 50 |
| Down-load resistance: ≤5Ω | ||
3) output (safe-area signal)
● Current output: current: DC 4~20mA,
Load resistance: ≤350Ω
● Voltage output: voltage: DC 1~5V,
Load resistance: ≥10 KΩ
4) Intrinsic safety:
● Explosion-proof: [Exib]ⅡC
● Max. voltage Um: 242V
● Max. output voltage Uo: 28V
● Max. output current Io: 118mA
● Max. external inductance Lo: 7mH
● Max. external Capacity Co: 0.083μF
5) Environmental parameters:
● Power supply: DC24V±10%, current consumption 1W when aftereffect Wpp < 10%
● Temperature for operating: 0 ~ +50 ℃
● Humidity: 0%~95%RH (none congeal)
2. Performance index (to full span)
● Standard accuracy: ±0.1% FS
● Temperature drift: ±0.015%/℃
● Response time: ≤1s (0→90%)
● Power voltage affect: ±0.1%/permitted voltage range
● Insulated resistance:
Input, output and power supply are isolated from each other ≥100 MΩ/DC 500V
● Isolation intensity: input-output-power supply-ground:
DC 1500V/1 minute (DC power)
AC 1500V/1 minute (AC power)
● load resistance affect: ±0.1%/250Ω (when current output)
±0.1% (when voltage output)
● Settling time: ≤3s
3. Construction and dimension
● Structure: compact, insert-mounting
● Connection: 3mm connection terminal
● Terminal screw material: nickel plating around surface of iron
(Screw arrowed wrest<0.8N•m)
● Shell material: burn-bear colophony
● Isolation: channel isolation (input,output and power supply are isolated from each othe)
● Zero adjustments-range: -5 ~ +5%
● Span adjustments-range: 95~105%
● Power indicate light: green LED, light on when power supply
● Mounting: DIN rail
● Outline dimension (W×H×D): 25×80×80mm
● Net weight: app. 150 g
« SLU-B11 (TypeS) Safety Isolated Barriers SLU-AB22 (TypeF) Safety Isolated Barriers »