Sensor Mod. |
CHF-50AS、100AS、200AS、300AS |
||||||
Description |
The SENSOR Module CHF-AS is an open loop Hall current sensor to measure 50A…300A DC, AC or pulsed currents with a galvanic isolation between the primary and secondary circuits. |
||||||
|
|||||||
Open-loop Hall Current Sensor: |
|||||||
Type |
Nominal current |
Output voltage |
Accuracy |
Supply voltage |
Aperture |
||
IN(A) |
VM(V) |
X(%) |
Vc(V) |
mm |
|||
CHF-50AS |
50 |
±4 |
±1.0% |
±12~15 |
φ16 |
||
CHF-100AS |
100 |
|
|
|
|
||
CHF-200AS |
200 |
|
|
|
|
||
CHF-300AS |
300 |
|
|
|
|
||
|
|||||||
Specifications: |
|||||||
Principle |
Open loop Hall effect principle |
||||||
Input current |
50…300A(DC、AC、Pulsed current) |
||||||
Output voltage |
±4V |
||||||
Frequency |
DC~20KHz |
||||||
Accuracy |
1.0% |
||||||
Response time |
<10μS |
||||||
Linearity |
1.0% |
||||||
Supply voltage |
±12V...15V(±5%) |
||||||
Consumption |
25mA |
||||||
Isolation voltage |
Between primary and secondary circuit: 2.5KV RMS/50Hz/1min. |
||||||
Operating temp. |
-10℃ …+85℃ |
||||||
Applications |
The sensors are used in the industry field of power supplies, welding machines, converters, |
||||||
|
industry auto-control, motor drives, electronic power system, railways, rectifiers systems etc. |
||||||
|
|||||||
Dimensions(mm) & Connection: |
|||||||
|
|||||||
|
|||||||
Typical Applications: |
|||||||
|
« SCHF-50E, 100E, 200E, 300E Open-loop Hall effect current sensor SCHK-100R,200R,400R,600R,800R Open-loop Hall effect current sensor »
Contact: Mr. Jason Zeng
sales@zntar.comzntarjason@gmail.com