Sensor Mod. |
CHB-2KC、3KC |
||||
Description |
The SENSOR Module CHB-2KC, 3KC is a closed loop Hall current sensor to measure2000A…3000A DC, AC or pulsed currents with a galvanic isolation between the primary and secondary circuits. The aperture can be opened by a structure of a split core for easy installation. |
||||
|
|||||
Closed-loop Hall Current Sensor: |
|||||
Type |
Nominal current |
Output current |
Accuracy |
Supply voltage |
Aperture |
IN(A) |
IM(mA) |
X(%) |
Vc(V) |
mm |
|
CHB-2KC |
2000 |
400 |
±0.4% |
±24 |
30x140 |
CHB-3KC |
3000 |
600 |
±0.4% |
±24 |
30x140 |
|
|||||
Specifications: |
|||||
Principle |
Closed loop Hall effect principle |
||||
Input current |
2000A…3000A(DC、AC、Pulsed current) |
||||
Output current |
400mA/600mA |
||||
Turns ratio |
1:5000 |
||||
Frequency |
DC~20KHz |
||||
Accuracy |
±0.4% |
||||
Response time |
<1μS |
||||
Linearity |
<0.1% |
||||
Supply voltage |
±24(±5%) |
||||
Consumption |
60mA+IM(Output current) |
||||
Isolation voltage |
Between primary and secondary circuit: 6KV RMS/50Hz/1min. |
||||
Operating temp. |
-25 …+70℃ |
||||
Applications |
The sensors are used in the industry field of power supplies, welding machines, converters, |
||||
|
industry auto-control, motor drives, electronic power system, railways, rectifiers systems etc. |
||||
|
|||||
Dimensions(mm) & Connection: |
|||||
|
« SCHB-4KB, 5KB, 6KB Closed-loop Hall effect current sensor SCHB-4000T Closed-loop Hall effect current sensor »
Contact: Mr. Jason Zeng