Sensor Mod. |
CHB-50SE、100SE、200SE |
||||||
Description |
The SENSOR Module CHB-50SE, 100SE, 200SE is a closed loop Hall current sensor to measure50A…200A DC, AC or pulsed currents with a galvanic isolation between the primary and secondary circuits. |
||||||
|
|||||||
Closed-loop Hall Current Sensor: |
|||||||
Type |
Nominal current |
Output current |
Accuracy |
Supply voltage |
Aperture |
||
IN(A) |
IM(mA) |
X(%) |
Vc(V) |
mm |
|||
CHB-50SE |
50 |
50 |
±1.0% |
±12…18 |
φ20 |
||
CHB-100SE |
100 |
100 |
±0.8% |
±12…18 |
φ20 |
||
CHB-200SE |
200 |
100 |
±0.8% |
±12…18 |
φ20 |
||
|
|||||||
Specifications: |
|||||||
Principle |
Closed loop Hall effect principle |
||||||
Input current |
50…200A(DC、AC、Pulsed current) |
||||||
Output current |
50mA/100mA |
||||||
Turns ratio |
1:1000(50A…100A);1:2000(200A) |
||||||
Frequency |
DC~100KHz |
||||||
Accuracy |
±0.8%~1.0% |
||||||
Response time |
<1μS |
||||||
Linearity |
<0.1% |
||||||
Supply voltage |
±12V…18V(±5%) |
||||||
Consumption |
10mA+IM(Output current) |
||||||
Isolation voltage |
Between primary and secondary circuit: 3KV RMS/50Hz/1min. |
||||||
Operating temp. |
0…+70℃ |
||||||
Applications |
The sensors are used in the industry field of power supplies, welding machines, converters, |
||||||
|
industry auto-control, motor drives, electronic power system, railways, rectifiers systems etc. |
||||||
|
|||||||
Dimensions(mm) & Connection: |
|||||||
|
|||||||
|
|||||||
Typical Applications: |
|||||||
|
« SCHB-50SF, 100SF, 200SF, 300SF Closed-loop Hall effect current sensor SCHB-100T Closed-loop Hall effect current sensor »
Contact: Mr. Jason Zeng
sales@zntar.comzntarjason@gmail.com